• ADM loop technology with
System Sensor/200 protocol
• Available with pane of glass or plastic
• LED indicates activation
• Versions with or without dual-isolator
• Operating instructions by means of
standardised symbols
Description
The Manual Call Points Series MCP5A are certified to Each of these two mechanical versions is available with
the standard EN 54-11/A and are designed for use in or without dual-isolator. The integrated dual-isolator dis-
ADM loops with System Sensor/200 protocol.
connects the adjacent loop elements fast and safely in
Two mechanical versions of the detector are available: case of a short circuit.
• With pane of glass: The detector is activated by
pressing in the pane of glass, which breaks into The activated condition of the manual call point is opti-
two pieces at a predetermined breaking point. By cally indicated by an LED. The detector address is se-
means of a special key, the detector case can be lected with two decadic rotary switches.
opened and the pane of glass can be replaced.
• With pane of plastic: The detector is activated by The detector is fitted into a plastic case and can be
pressing in the pane of plastic without breaking it. mounted on a 60mm flush-mount installation box. An
By means of a special key, the pane can be put optional case for surface mounting on a wall can be
back to the idle position, thereby resetting the de- supplied.
tector.
Specifications
Operating voltage
Ambient temperature
Relative humidity
Protection class
Dimensions W × H × D
Colour
Supply through loop voltage
-10°C to +55°C (no condensation or icing)
max. 95% (no condensation)
IP24
89 × 93 × 28 (mm)
flame red, RAL 3000
110g
Weight
Approval
LPCB 166b/45, 166b/46
Manual call point with pane of glass, without isolator MCP5A-RP07FG
Current consumption
Order number
260µA (quiescent)
245040
Order name
Manual Call Point/Red/200/Glass MCP5A-RP07FG
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
MCP5A_DBL_LST_EN_0804.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
La Crosse Technology Clock WT 3181pl User Manual
Lexmark All in One Printer X460 Series User Manual
Lexmark Printer Z43 User Manual
LG Electronics Air Conditioner LS122CE User Manual
Lowrance electronic GPS Receiver Expedition C User Manual
Magnavox TV VCR Combo CCZ252AT User Manual
Makita Nail Gun AF631 User Manual
Master Bilt Freezer DC 10D User Manual
Melissa Fan 671 127 User Manual
Mercedes Benz Automobile 2003 M Class User Manual